Mix design M 40


Mix Design of M40 mix concrete by IS method:

(a) Design stipulations:
Characteristic compressive strength required in the field at 28 days.
40 MPa
Maximum size of aggregate
20 mm (angular)
Degree of quality control
Good
Type of Exposure
Mild

(b) Test data for Materials:
Specific gravity of cement
3.15
Compressive strength of cement at 7 days
Satisfies the requirement of IS: 269 – 1989
1. Specific gravity of coarse aggregates
2.60
2. Specific gravity of fine aggregates
2.60
Water absorption:

1. Coarse aggregate
1.0%
2. Fine aggregate
1.0%
Free (surface) moisture:

1. Coarse aggregate
Nil
2. Fine aggregate
2.0%

(c) Target mean strength of concrete:

The target mean compressive (ft) strength at 28 days is given by
ft = fck + 1.65 S
i.e. 40 + 1.65 x 5 = 48.25 MPa




(d) Selection of water-cement ratio:

The water-cement ratio required for the target mean strength of 48.25 MPa is 0.40. Adopt W/C ratio of 0.40.
(e) Selection of water and sand content:
For 20 mm maximum size aggregate, sand confirming to grading Zone II, water content per cubic metre of concrete = 180 kg and sand content as percentage of total aggregate by absolute volume = 25 per cent.
Required water content = 180 + 5.4 = 185.4/m3

(f) Determination of cement content:

Water-cement ratio = 0.40
Water = 185.4 litre
Cement by mass = Water content/Water cement ratio
Cement = 185.4/0.40 = 463.5 kg/m3
This cement content is adequate for ‘mild’ exposure condition.

(g) Determination of coarse and fine aggregate contents:
For the specified maximum size of aggregate of 20 mm, the amount of entrapped air in the wet concrete is 2 per cent. Taking this into account and applying equations.
formula-for-concrete-mix-design
Where V = absolute volume of concrete = gross volume (1m3) minus the volume of entrapped air
           Sc = specific gravity of cement
              W = Mass of water per cubic metre of concrete, kg
            C = mass of cement per cubic metre of concrete, kg
            p = ratio of fine aggregate to total aggregate by absolute volume
     fa, Ca = total masses of fine and coarse aggregates, per cubic metre of concrete, respectively, kg, and
  Sfa, Sca = specific gravities of saturated surface dry fine and coarse aggregates, respectively
fa = 530.27 kg/m3, and
Ca = 1153.13 kg/m3.

The mix proportion then becomes:
Water
Cement
Fine aggregate
Coarse aggregate
185.4
463.5 kg
530.27 kg
1153.13 kg
0.40
1             
1.14               
2.49

(h) Actual quantities required for the mix per bag of cement:
The mix is 0.40: 1: 1.14: 2.49.
For 50 kg of cement, the quantities of materials are worked out as below:
                i.            Cement = 50 kg
              ii.            Sand = 57 kg
             iii.            Coarse aggregate = 124.5 kg                     
            iv.            Water:
a)      for w/c ratio of 0.40, quantity = 20 litres of water
b)      Extra quantity of water to be added for absorption in case of CA, at
0.5 per cent mass = 0.62 litres
c)      Quantity of water to be deducted for moisture present in sand, at
2 per cent by mass = 1.14 litres.
d)      Actual quantity of water required to be added = 20 + 0.62 – 1.14
                                                                                          = 19.48 litres
 Actual quantity of sand required after allowing for mass of free moisture = 57 + 1.14
                                                                                                               = 58.14 kg
Therefore, the actual quantities of different constituents required for one bag mix are:
Water          :         19.48 litres
Cement       :         50.00 kg
Sand           :          58.14 kg
Coarse Aggregates: 124.5 kg

18 comments:

  1. hi which calculation did you used to get this quantity in cubic meters

    ReplyDelete
  2. hi which calculation did you used to get this quantity in cubic meters

    ReplyDelete
  3. Material should be of good quality were use in the part of construction, mostly the quality of construction will depend on this only. Thanks for share nice Stuff
    concrete mix design procedure

    ReplyDelete
  4. we are offers to Mix design of concrete Design stipulations and Test data for Materials service at good price.You are a great adviser. Thanks for advising these simple tools.
    Waterproof concrete

    ReplyDelete
  5. For more information regarding Specific Gravity of Cement read:
    Specific Gravity of Cement- Details and Test Procedure

    ReplyDelete
  6. Is it convenient for pump able for post tensioning beams ?

    ReplyDelete
  7. This comment has been removed by the author.

    ReplyDelete
  8. As per IS 456-2000, Clause 8.2.4.2, the maximum cement content should not be more than 450 kg/cu.m.

    ReplyDelete
  9. Very well done. Absolutely brilliant information. I'm in love with this blog. they always provide such a great information. sand and cement mix


    ReplyDelete
  10. could you tell me the ratio for 40 mpa. is it 2 parts cement 2 parts sand 4parts 10mm aggregate and how much water. i await your reply.

    regards nick

    ReplyDelete
  11. I learn some new stuff from it too, thanks for sharing your information. Concrete services

    ReplyDelete
  12. Wow such a nice article, thanks for this post you should know about Complete Guide on Grades of Concrete

    ReplyDelete
  13. Great post, and great website. Thanks for the information! concrete contractors york pa

    ReplyDelete
  14. You have worked admirably on this article. It's truly meaningful and profoundly wise. You have even figured out how to make it justifiable and simple to peruse. You have some genuine composition ability. Much thanks to you. concrete contractors Plano

    ReplyDelete
  15. 온카지노 온카지노 rb88 rb88 sbobet ทางเข้า sbobet ทางเข้า 카지노사이트 카지노사이트 クイーンカジノ クイーンカジノ 메리트카지노 메리트카지노 happyluke happyluke 996

    ReplyDelete